Carrier · Air handler troubleshooting
Convert to downflow or horizontal right installation
What is going on
Field conversion of the air handler from upflow to downflow or horizontal right orientation. Disconnect power before starting.
Check in this order
- Turn off and lock out power before working on the unit.
- Remove the filter door and filter.
- Remove the upper cover assembly.
- Open the electronic control box cover and remove the evaporator cover plate, then the bottom cover and second cover plate.
- Unplug T1, T2, T2A, T2B, the refrigerant detection sensor and the EEV from the control board.
- Remove the sensor, EEV and refrigerant detection sensor wire ties.
- Remove the evaporator and drain pan and rotate them 180° for vertical down configuration.
- Adjust the mounting parts to match the new airflow direction.
- Reinstall the evaporator and drain pan.
- Reconnect the T1, T2, T2A, T2B sensor plugs and EEV, then tie up the sensor wires.
- Cut the foam gasket and remove knockouts; route the wire through the buckle and wire slot, then replace the foam gasket over the wires.
- Attach the room temperature sensor with cable ties.
- Reconnect the wiring per the wiring diagram.
- Reassemble the upper cover and filter cover plate.
- Connect the refrigerant pipes and drain pipes.
Applies to: D5FUAA downflow and horizontal right installations
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FUAA installation instructions, p. 34-37. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.