Carrier · Air handler troubleshooting
Convert the air handler from 230 V to 115 V supply
What is going on
Field change of the motor plug and the 24 V transformer connection. Start from the factory 230 V default.
Check in this order
- Unplug the white 230 V connector from the fan motor wire. Connect the red 115 V connector to the fan motor wire.
- Unplug these connectors from the main control board: CN11 (power wire), CN15 and CN34 (fan motor), CN22 (EEV), CN26 (refrigerant sensor), CN46 (T1 sensor), CN47 (T2 sensor), and CN7 (T2A and T2B sensors).
- Remove the two screws holding the control box and pull the control box out of the cabinet.
- Unplug the default 230 V connection wire (red connector) from the 24 V transformer and from port CN12 on the main control board.
- Install the 115 V connection wire: connect its white connector to the 24 V transformer and its other connector to CN12 on the main control board.
- Reinstall the control box in the cabinet, fix it with screws, and seat the wire body properly.
- Reconnect the temperature sensors T1, T2, T2A and T2B, the refrigerant detection sensor, the EEV, and the fan motor power pair plug (CN11).
- Reconnect all other connectors removed in step 2.
Applies to: D5FUAA sizes 18K to 60K, 115 V power supply
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FUAA installation instructions, p. 20-22. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.