Carrier · Air handler troubleshooting

Condensate drain connection and trap

D5FULA

What is going on

The coil pan has two 3/4 in female connections. A trap is not needed on the supply side of the furnace, but local codes may require one.

Check in this order

  1. Use PVC fittings on the condensate pan. Finger tight plus 1-1/2 turns; do not overtighten.
  2. Install a plastic plug in any unused drain fitting.
  3. If a trap is required, place it as close to the coil as possible, with the outlet below the pan connection to prevent overflow.
  4. Prime all traps, check for leaks and insulate traps and lines that run above living space.
  5. Keep aluminum tubing from touching dissimilar metals or letting condensate run onto them to avoid galvanic corrosion.

Applies to: D5FULA condensate drain

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5FULA installation instructions, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.