Carrier · Air handler troubleshooting
Condensate drain connection and trap
What is going on
The coil pan has two 3/4 in female connections. A trap is not needed on the supply side of the furnace, but local codes may require one.
Check in this order
- Use PVC fittings on the condensate pan. Finger tight plus 1-1/2 turns; do not overtighten.
- Install a plastic plug in any unused drain fitting.
- If a trap is required, place it as close to the coil as possible, with the outlet below the pan connection to prevent overflow.
- Prime all traps, check for leaks and insulate traps and lines that run above living space.
- Keep aluminum tubing from touching dissimilar metals or letting condensate run onto them to avoid galvanic corrosion.
Applies to: D5FULA condensate drain
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5FULA installation instructions, p. 23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.