Upflow coil installation
What is going on
Set the cased coil on the furnace discharge opening and check that it is level.
Check in this order
- Set the coil on the upflow furnace discharge air opening.
- Check that the coil is level for proper condensate drainage. Do not tip it toward the drain.
- The casing does not need to be fastened to the furnace.
- If a wider coil sits on a narrower furnace, build a field-fabricated adapter.
- Keep at least 4 in. clearance as shown in the figures on the coil and furnace.
- If the coil is in an unconditioned space, wrap a 6 in. wide insulation strip around the casing and supply duct contact point.
Applies to: Upflow installations
More air conditioner guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLFULA Installation Instructions, pp. 10, 12. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.