Checking room area against refrigerant charge

D5FUHA

What is going on

Room area limits for an A2L/R454B system serving a room or ducted rooms.

Check in this order

  1. Measure room area A from the floor projection of walls, partitions and doors.
  2. Do not count spaces joined only by drop ceilings, ductwork or similar connections as one room.
  3. Keep the air duct outlet in the room at 7.2 ft (2.2 m) or higher from the floor.
  4. Compare actual charge Mc with the allowable maximum charge for the room area (Table 6).
  5. For connected rooms, check total conditioned area TA against TAmin.
  6. Make sure the room the unit is in is at least 20% of TAmin.
  7. Provide openings per Table 6 and the opening conditions, with 50% of Anvmin below 200 mm from the floor.

Applies to: R454B charge limits and room sizing

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5FUHA installation instructions, p. 10-12. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.