Checking room area against refrigerant charge
What is going on
Room area limits for an A2L/R454B system serving a room or ducted rooms.
Check in this order
- Measure room area A from the floor projection of walls, partitions and doors.
- Do not count spaces joined only by drop ceilings, ductwork or similar connections as one room.
- Keep the air duct outlet in the room at 7.2 ft (2.2 m) or higher from the floor.
- Compare actual charge Mc with the allowable maximum charge for the room area (Table 6).
- For connected rooms, check total conditioned area TA against TAmin.
- Make sure the room the unit is in is at least 20% of TAmin.
- Provide openings per Table 6 and the opening conditions, with 50% of Anvmin below 200 mm from the floor.
Applies to: R454B charge limits and room sizing
More air conditioner guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5FUHA installation instructions, p. 10-12. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.