Carrier · Air conditioner troubleshooting
Charging a system with flammable refrigerant
What is going on
Charging and leak-test steps for R454B / flammable refrigerant systems.
Check in this order
- Use only tools approved for flammable refrigerants.
- Keep charging hoses as short as possible.
- Make sure charging equipment does not contaminate refrigerants.
- Keep cylinders upright.
- Earth the refrigeration system before charging.
- Do not overfill the system.
- Pressure test with oxygen-free nitrogen (OFN) before recharging.
- Leak test after charging and before commissioning.
- Run a follow-up leak test before leaving the site.
- Label the system when charging is complete.
Applies to: Flammable refrigerant systems
More air conditioner guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5FUHA installation instructions, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.