Carrier · Air conditioner troubleshooting

Downflow coil installation

DLFULA

What is going on

Downflow installs need an adapter when the coil is rotated 90 degrees.

Likely causes

  • Rotating an A coil 90 degrees causes uneven air on the coil slabs, which can cause water blow-off or coil freeze-up.

Check in this order

  1. Set the cased coil on the supply duct opening.
  2. Place a field-fabricated adapter of at least 4 in. on the coil casing, tapered if the coil and furnace sizes differ.
  3. Set the furnace on the adapter.
  4. On a 4-way multipurpose furnace, break off the perforated duct flanges as described in the furnace instructions.
  5. If airflow is high and water blow-off is possible, use a 4 in. minimum adapter between coil and furnace.

Applies to: Downflow installations, especially coils rotated 90 degrees

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFULA Installation Instructions, p. 12. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.