Downflow coil installation
What is going on
Downflow installs need an adapter when the coil is rotated 90 degrees.
Likely causes
- Rotating an A coil 90 degrees causes uneven air on the coil slabs, which can cause water blow-off or coil freeze-up.
Check in this order
- Set the cased coil on the supply duct opening.
- Place a field-fabricated adapter of at least 4 in. on the coil casing, tapered if the coil and furnace sizes differ.
- Set the furnace on the adapter.
- On a 4-way multipurpose furnace, break off the perforated duct flanges as described in the furnace instructions.
- If airflow is high and water blow-off is possible, use a 4 in. minimum adapter between coil and furnace.
Applies to: Downflow installations, especially coils rotated 90 degrees
More air conditioner guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLFULA Installation Instructions, p. 12. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.