Carrier · Air conditioner troubleshooting

Refrigerant line connection and brazing

DLFULA

What is going on

Connect the field tubing to the coil stubs. Evacuate and reclaim as needed, and leak check before insulating.

Likely causes

  • Factory nitrogen charge may leak past the rubber plugs in storage; this does not mean the coil leaks.

Check in this order

  1. Remove the cabinet access door. Install the door before brazing on coils that have no serviceable service door.
  2. Remove the suction plug first, then the liquid plug, with a pulling and twisting motion. Hold the stubs steady.
  3. Slide the tubing plate with grommets onto the field lines, away from the joints.
  4. On heat pumps, install a filter drier on the liquid line. Replace it any time the system has been opened to air. Use only factory-specified drier rated under 600 psig. Do not install a suction-line drier in the liquid line.
  5. Wrap the drier with a damp cloth and flow nitrogen while brazing.
  6. Fit the lines into the stubs and wrap a heat sink (wet cloth) behind the joints and around the TXV and nearby tubing.
  7. Purge with 1/2 psig nitrogen through the suction line and out the liquid line while brazing.
  8. Braze with Sil-Fos or Phos-copper alloy. Do not use soft solder.
  9. After cooling, make sure the TXV bulb is secure with a hose clamp. Tighten the screw a half turn past hand tight, seat the bulb on the vapor line, and re-wrap the insulation.
  10. Leak check the connections before insulating the whole suction line.
  11. Slide the grommet plate over the joints, center the tubing in the grommets, and reinstall the cabinet door.

Applies to: Refrigerant tubing connections

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFULA Installation Instructions, p. 13. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.