Carrier · Air conditioner troubleshooting
Horizontal coil installation
What is going on
The coil can be set on a work platform, roof truss, floor joist hangers or blocks. It allows airflow in either direction.
Check in this order
- Make sure the coil cabinet is level side to side and front to back.
- Up to 1/2 in. of extra slope over the cabinet length and depth is allowed toward the drain pan connection.
- For horizontal right fit field attachment plates, screw them to the casing, connect the furnace snugly, seal the joint airtight with approved materials, and seal the pan extension with cork tape.
- Install the included condensate pan extension and two corner screws.
- For horizontal left unbend the 4 tabs on the right side of the casing, connect the furnace snugly, and seal the joint airtight.
- If the coil is wider than the furnace, use a 4 in. minimum transition.
Applies to: Horizontal left and right installs
More air conditioner guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLFULA Installation Instructions, p. 12. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.