Economizer won't engage. Usually a missed condition, not a dead part. Walk the checklist.
Likely causes
- Outdoor air not at or below the cut-in temperature
- No cooling call, or humidity above the limit on an enthalpy control
- Damper relay or free-cooling damper not energized, or blower off, or relief damper stuck
Check in this order
- Check the outdoor sensor reads at or below cut-in, for example 65°F
- Confirm the indoor space actually needs cooling
- Confirm humidity is below the limit if the control uses enthalpy
- Check Y1 energizes the damper relay or free-cooling damper
- Confirm the blower is running
- Verify the barometric relief damper opens
- Meter 24 V at the damper actuator when all conditions are met
More air conditioner guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.