Freezing in cold weather
What is going on
Water freezing on an outdoor cooling tower or evaporative unit in cold weather. It typically happens at low load and cold ambient, and it starts in the corners where flow is lowest. Ice can damage fill, louvers and fan parts.
Likely causes
- Low load with cold ambient air
- Ice starting at the corners where flow is lowest
- Leaving water too cold
- Exposed piping with no heat trace
- Basin heater off or undersized
Check in this order
- Keep leaving water at about 40°F.
- Install basin heaters.
- Add heat-trace on exposed piping.
- Use an indoor reservoir where possible.
- Watch the corners and fill for ice buildup during cold spells.
- Never reverse the fans, as ice forms on the intake and can damage the unit.
More air conditioner guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.