Bubbles in sight glass / temperature drop across liquid line drier
What is going on
Possible causes and checks for: bubbles in sight glass / temperature drop across liquid line drier.
Likely causes
- Plugged liquid line drier (restriction), low charge, unloaded compressor, normal start/stop equalization, flash gas from warm liquid
Check in this order
- ΔT across drier (restriction = cold outlet/frost), subcooling, charge, wait for steady state
More air conditioner guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.