Bubbles in sight glass / temperature drop across liquid line drier

What is going on

Bubbles in the sight glass do not always mean low charge. Before adding refrigerant, confirm whether the liquid line drier is restricted, and whether the unit is simply in a normal transition such as start-up or an unloaded compressor. Adding refrigerant on a false reading leads to an overcharge, so measure first and call a licensed tech for any recovery or charging.

Likely causes

  • Plugged liquid line drier causing a restriction
  • Low charge
  • Unloaded compressor, which can show bubbles at reduced load
  • Normal start and stop equalization
  • Flash gas from warm liquid, with low subcooling

Check in this order

  1. Measure the temperature difference across the drier with two thermometers. A restriction shows as a cold outlet or frost.
  2. Take subcooling at the condenser outlet, since low subcooling suggests charge or condenser trouble
  3. Confirm the compressor is fully loaded before judging the sight glass
  4. Wait for steady state after start-up before reading anything
  5. If the drier is restricted, recover the charge and replace it, never reuse it
  6. Recheck sight glass, subcooling and drier temperature drop after the repair

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.