All brands · Air conditioner troubleshooting
Coil iced, airflow blocked, poor cooling, high box temp
What is going on
Iced coil, blocked airflow, box running warm. Defrost is not doing its job, or the coil design is wrong for the application.
Likely causes
- Defrost never starts: timer motor dead, or the wrong timer type or wiring for the system
- Heater or hot-gas solenoid failed, so defrost starts but no heat gets to the coil
- Termination thermostat failed, ending defrost early or never
- Too few defrosts per day, or defrost too short
- Fin spacing too tight for the application, so frost bridges the fins fast
- High TD across the coil, which pulls more moisture out of the air
Check in this order
- Advance the timer by hand and see if the defrost contactor pulls in, because that proves whether the timer works at all
- Compare the wiring to the timer type time-time, time-temp or time-pressure, since a mismatch gives odd behavior
- Measure heater amps and continuity with power off and locked out for the continuity check
- Check the hot-gas solenoid coil for voltage and continuity, and listen for it to shift
- Test the termination switch, it should close cold and open at its set temperature
- Review defrost frequency and duration against the load and add cycles if frost returns before the next one
More air conditioner guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.