Continuous run, no cooling, condenser cooler than normal
What is going on
Unit runs and runs and never catches up, and the condenser feels cooler than it should. In my experience that points to a restriction on the high side, where refrigerant can't get through to the evaporator, so the condenser isn't loaded with heat the way a healthy system would be. Always find the pinch point before you start adding gas.
Likely causes
- High-side restriction, usually a plugged filter drier or screen, or a kinked or clogged cap tube
- Moisture or debris left over from a past repair that has collected at the smallest opening
Check in this order
- Isolate the restricted section with a nitrogen pressure test and check for a temperature drop across the drier or cap tube
- Recover the refrigerant under proper procedure, as a licensed tech must
- Replace the drier every time the system is opened, no exceptions
- Replace the cap tube if it is the plugged part
- Evacuate, recharge by weight and confirm normal pressures and condenser temperature
More air conditioner guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.