Undercharged system: compressor runs continuously, poor cooling, high power use, warm liquid line and drier
What is going on
Undercharged unit. Compressor runs nonstop, cooling is weak, amps and power bill climb. Liquid line and drier feel warm because the high side is not condensing properly. Classic low charge. Find the leak first, then fix the charge.
Likely causes
- Low charge, so the condenser cannot build enough liquid and the high side is not condensing
- Leak somewhere in the circuit that has been bleeding refrigerant off
Check in this order
- Feel the liquid line and drier, a warm drier means a problem
- Note a hot drier can release trapped moisture back into the system
- Hook up gauges and compare with a P/T chart for the refrigerant in use
- Find and fix the leak before adding anything
- Recharge by weight and verify superheat or subcooling
- Consider fitting a new drier while the system is open
More air conditioner guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.