Carrier · Air conditioner troubleshooting

Two-stage unit not changing stages - Carrier 24ANB/25HNB/25HCB6

What is going on

Unit runs but capacity does not seem to change between low and high stage.

Likely causes

  • Unloader solenoid not getting 24 V DC
  • Solenoid plug without internal rectifier
  • Open or grounded unloader coil
  • Control or thermostat not calling Y2

Check in this order

  1. Watch suction pressure it should fall roughly 3-10 percent going to high stage; do not judge by liquid pressure.
  2. Compressor amps should rise 20-45 percent in high stage.
  3. Cycle low/high at 30 s or longer intervals and read amps 5 s after the change; at least 20 percent change is expected.
  4. No change unplug the solenoid plug and check for 24 V DC while high stage is called.
  5. Voltage good measure the coil; about 330 or 1640 ohms is normal - open or grounded means compressor replacement.
  6. Only use a solenoid plug with the built-in rectifier.

Applies to: 24ANB1, 24ANB7, 25HNB6, 25HNB9, 25HCB6, CH17

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier Residential AC & HP Application Guideline and Service Manual 24-25-9SM (text export), Unloader Test Procedure. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.