Amber STATUS or green COMM light not on

What is going on

Two little lights on the outdoor board of your Carrier Infinity 19VS (24VNA9) can tell you a lot. The amber STATUS light and the green COMM light on the AOC board show whether the board has power and whether it is talking to the indoor unit. If the amber light is off with power on, the board is most likely dead. The green light is a bit different, because with a non-communicating thermostat it is normally off, so check what you have before you start swapping parts. Wall control code 179 is a good hint too.

Likely causes

  • AOC board failure
  • No communication with the indoor unit or wall control
  • Non-communicating thermostat, where the COMM light is normally off
  • A and B communication wires open, loose or swapped

Check in this order

  1. With power to the outdoor unit the amber STATUS light must be on or flashing, if it is completely off, confirm the unit has supply voltage and then replace the AOC board
  2. Communicating systems the green COMM light should be on steady once the indoor unit and Infinity control talk to it, it goes off after 2 minutes without communication
  3. If A and B wires are connected and the indoor unit communicates but COMM stays off, replace the AOC board
  4. Check the A and B wires at both ends for tight connections
  5. Wall control code 179 means lost communication with the outdoor AOC, the AOC or inverter may need replacing
  6. Turn power off at the disconnect before working on the wiring

Applies to: Carrier Infinity 19VS variable speed air conditioner 24VNA9

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier 25VNA8 / 24VNA9 Service Manual, Communication and Status Function Lights p.8; LED tables p.27-28. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.