Carrier · Air conditioner troubleshooting
Delay before the compressor restarts
What is going on
The outdoor unit waits a while before it starts again after stopping. On the Carrier Infinity 19VS (24VNA9) that is usually normal. It is protection built into the control, so it is not a failure, and it covers equalizer cycles, warm-up after power-up and fault delays.
Likely causes
- Pressure equalizer valve cycle after every compressor stop
- 10-minute warm-up after high voltage power-up
- Protection delays from fault codes
- Brown-out recovery delay after a low voltage event
Check in this order
- After every compressor stop the pressure equalizer valve opens for 150 s, then 15 s off before the next start, this cannot be bypassed, because it protects the compressor from starting against high head pressure
- After power-up the compressor sump warms for 10 minutes (code 68), because refrigerant in the oil needs to boil off
- Check the STATUS light for any other fault delay and look up the code
- The brown-out recovery delay can be cleared using the Forced Defrost pins as the manual describes, confirm supply voltage is good first and follow the literature exactly
- If delays keep coming back, meter the line voltage at the unit for sags
- Tell the homeowner the wait is normal
Applies to: Carrier Infinity 19VS variable speed air conditioner 24VNA9
More air conditioner guides
- Amber STATUS or green COMM light not on
- Compressor will not run - winding and electrical checks - Carrier split systems
- Hissing from the outdoor unit after it shuts off
- Outdoor unit unresponsive after several faults
- Superheat too high or too low on TXV system - Carrier split systems
- Two-stage unit not changing stages - Carrier 24ANB/25HNB/25HCB6
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier 25VNA8 / 24VNA9 Service Manual, Timing / delays p.8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.