Carrier · Air conditioner troubleshooting

Outdoor unit unresponsive after several faults

What is going on

Carrier Infinity 19VS air conditioner (24VNA9) quits responding after a string of fault codes. Nothing is broken. Control just latches. Happens now and then.

Likely causes

  • Control latched after earlier faults
  • Stale fault memory from a power blip or tripped protection

Check in this order

  1. Kill high voltage to the outdoor unit at the disconnect for at least 2 minutes, then restore it.
  2. Wait out the 10-minute sump warm-up delay after power-up (code 68). Normal, not a fault.
  3. Still dead? Go to the STATUS light codes.
  4. If the same codes come back after a reset, the problem is real, so chase it.

Applies to: Carrier Infinity 19VS variable speed air conditioner 24VNA9

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier 25VNA8 / 24VNA9 Service Manual, Status Codes note p.14. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.