Superheat above target

What is going on

High superheat on an air conditioner. The evaporator is starved, so the vapor leaving it picks up too much heat.

Likely causes

  • Undercharge
  • Liquid-line restriction
  • Metering device underfeeding
  • Moisture in the system freezing at the orifice
  • Excessive heat load

Check in this order

  1. Leak check and charge, because low charge starves the evaporator
  2. Check temperature drop across the drier and liquid line to find a restriction
  3. Check the orifice or metering device
  4. Replace the drier and evacuate if moisture is suspected
  5. Check the load and airflow
  6. Re-measure superheat after the system settles

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.