All brands · Air conditioner troubleshooting

Poor performance

What is going on

Most weak-performance calls I see on evaporative and water-cooled gear come back to the water side. When nozzles or basin holes plug, the water doesn't spread evenly over the fill, so the unit can't throw off heat the way it's built to. Hot, humid weather exposes it first, and scale on the media just makes it worse every season.

Likely causes

  • Hot, humid ambient air that is simply asking more of the unit than usual
  • Clogged spray nozzles or plugged basin distribution holes
  • Uneven water distribution over the fill
  • Scale buildup on the media
  • Louvers throttled down and starving the unit of air

Check in this order

  1. Look at the water pattern over the fill and note any dry or flooded spots
  2. Clean the nozzles and basin holes and flush out the debris
  3. Descale the media and check what the water treatment has been doing
  4. Check louver position and open them up if they've been throttled
  5. If the fans are variable speed, confirm they ramp up as load climbs
  6. If it still falls short, look at getting more air or more water flow through the unit

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.