All brands · Air conditioner troubleshooting

Poor cooling, low suction, high superheat, warm evaporator

What is going on

When cooling is weak, suction is low, superheat is high and the evaporator feels warm, the system is being starved of refrigerant somewhere ahead of the coil. On a cap-tube system the usual story is a plugged tube. Look for frost right where the blockage is, because it tells you exactly where to look.

Likely causes

  • Cap tube plugged, from wax from overheated oil or burnout debris
  • Crimped or bent tube
  • Plugged filter-drier or strainer
  • Undercharge

Check in this order

  1. Look for frost on the cap tube and drier, since frost shows the restriction
  2. Measure suction pressure and compressor amps
  3. Compare the tube's condition against a straight one
  4. Replace the tube with the same length and inside diameter
  5. Fit a new liquid line drier at the same time
  6. Recover refrigerant properly, licensed technician only

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.