All brands · Air conditioner troubleshooting

Overcharged system

What is going on

An overcharged system has more refrigerant than the condenser and evaporator can handle, and what it does depends on the metering device. On a TXV system you mostly see high head pressure and poor efficiency. On a cap-tube system the extra liquid can push back down the suction line and flood the compressor, which is how compressors get damaged. Charging by feel or by guesswork is how most of these happen.

Likely causes

  • On a TXV system the extra liquid backs up in the condenser and drives head pressure up
  • On a cap-tube system liquid floods back to the compressor and risks damage
  • Topping off a system that was never actually low

Check in this order

  1. Read high and low side pressures and compare with the manufacturer's charging chart
  2. Check subcooling and superheat to confirm the overcharge instead of guessing
  3. Recover the excess refrigerant with a recovery machine, never vent it
  4. Recheck subcooling or superheat after each small removal
  5. Confirm the amp draw settles back to the nameplate range

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.