No cooling
What is going on
No cooling on a zoned system. Work from the stat to the panel to the condenser, since each step rules out a section.
Likely causes
- Zones not calling for cooling or master-slave switch not in cool
- Missing 24 Vac Y to C at the panel output, possibly a blown panel fuse
- Contactor, disconnect or control voltage problem at the condenser
Check in this order
- Set all zones to cool 5°F below room, with master-slave system switch on cool, because the panel delays the first call
- Wait out the minimum run time, then check the contactor
- If it isn't pulled in, meter 24 Vac Y to C at the panel output and check the panel fuse
- At the stat side, 24 V Y to C, 0 V R to Y and 24 V R to W confirms the panel and stats are fine
- At the condenser, meter 24 V across the contactor coil, then line voltage at the disconnect and top of the contactor
- Call a licensed tech for any line-voltage work
More air conditioner guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.