All brands · Air conditioner troubleshooting

No cooling via stat

What is going on

No cooling from the thermostat. Same check as the no-heat test, different terminals.

Likely causes

  • Thermostat not sending a cooling call to the contactor
  • No 24 V reaching the contactor or blower circuit
  • Open safety or wiring fault in the control circuit

Check in this order

  1. Turn power off, pull the thermostat from the subbase and inspect the wiring
  2. Power back up and meter R to Y, which is the contactor call
  3. Meter R to G for the blower call
  4. Follow the same procedure as the heating check #38, using R-Y and R-G in place of R-W
  5. No voltage at R-Y means trace upstream, voltage present means look at the contactor and outdoor unit
  6. Call a licensed tech for any line-voltage work at the condenser

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.