All brands · Air conditioner troubleshooting
No cooling, compressor runs, condenser fan off, very high head, compressor cycling on overload
What is going on
No cooling. Compressor runs but the condenser fan is dead, so heat has nowhere to go. Head pressure climbs and the compressor cycles on overload. Classic dead condenser fan, Scenario 32A. Shut it down, don't let it keep tripping.
Likely causes
- Condenser fan motor open winding, infinite ohms
- Bad run capacitor
- Dirty condenser coil adding to the high head
- Fan blade loose on the shaft or wrong rotation
Check in this order
- Power off and locked out, discharge the cap.
- Ohm the fan motor windings. Open means replace.
- Test the run cap with a meter and compare with its rating.
- Replace the fan motor if open.
- Check rotation direction.
- Clean the coil and recheck head pressure.
- Confirm the compressor stays on without tripping.
More air conditioner guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.