No cooling, compressor and condenser fan both dead, supply voltage present at disconnect
What is going on
No cooling, and both the compressor and the condenser fan are dead, but there is supply voltage at the disconnect. Voltage reaching the disconnect only tells you the supply is alive up to that point. After a storm, blown cartridge fuses are a common cause. Treat the disconnect as live until you have proven otherwise and wear proper PPE. Scenario 33A.
Likely causes
- Blown cartridge fuses, often after a storm
- Also check breakers
- Power outage upstream
Check in this order
- Pull the disconnect and check continuity of each fuse, infinite ohms means open
- Verify the line side is energized and the load side is not before touching anything
- Replace fuses with the same rating
- If they blow again, stop and have a licensed tech find the short
- Verify system pressures after restart
More air conditioner guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.