Measurable pressure drop across suction filter-drier; oil return problems, low suction, loss of capacity
What is going on
If you can measure a pressure drop across a suction filter-drier, it's restricted. Most times I see this after a compressor burnout, where acid and sludge got swept into the drier and it filled up with debris. The suction line gets starved, oil stops coming back and the unit loses capacity. Sometimes the drier is just too small for the suction velocity.
Likely causes
- Drier plugged with burnout debris
- Drier undersized, so velocity and pressure drop are too high
Check in this order
- Read pressure at the inlet and outlet access ports and compare the two. A real drop means a restriction.
- Replace the core, and do not reuse a loaded core
- Size the replacement for suction velocity and load, not just the line size
- Check oil level at the compressor, since a restricted drier means oil return trouble
- Test the oil for acid if a burnout is suspected
- Recheck drop across the new drier after a few hours of running
More air conditioner guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.