Low suction + high superheat (starved evaporator)
What is going on
Low suction pressure with high superheat means the evaporator is starved of refrigerant. Something upstream is limiting flow or the system is short of charge. Refrigerant recovery and recharge must be done by a licensed technician, and wear eye protection when handling it. Scenario 32E.
Likely causes
- Low charge or a leak
- TXV bulb lost its charge so the valve stays closed
- Plugged filter drier
Check in this order
- Inspect the TXV bulb and its mounting
- Replace the TXV and the liquid line drier if the bulb is bad
- Check the oil for acid
- Recover the refrigerant, evacuate and recharge to spec
- Find and repair any leak before recharging
More air conditioner guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.