All brands · Air conditioner troubleshooting
Low head pressure, starved evaporator, high superheat and high subcooling readings, short cycling, poor cooling in winter
What is going on
What I usually find on a winter complaint like this is head pressure control that isn't doing its job. When the outdoor air gets cold the condenser rejects too much heat, head pressure falls, and the metering device can't get enough liquid through. You see a starved evaporator, high superheat, high subcooling readings, short cycling and poor cooling. The cause is almost always the control side, not the compressor.
Likely causes
- No or failed head pressure control, such as a stuck louver bellows or linkage
- Fan cycling switch failed
- Fan speed control thermistor bad
- Receiver heater out, or an ORI/ORD/LAC valve stuck or set wrong
- Receiver too small to flood the condenser, or insufficient charge for winter flooding
- Split condenser valve not shifting, or a strong cold wind
Check in this order
- Compare head pressure with ambient temperature. Low head on a cold day points at the control.
- Watch the louvers move. A stuck bellows or linkage will not close them down.
- Check fan operation against pressure, ORI setting and the ORD at about 20 psi differential.
- Check the charge and receiver level in the sight glass, since flooding needs enough refrigerant.
- Check split valve position and the bleeder line.
- Check the check valves for leakage.
- Check the receiver heater and fan cycling switch or speed control sensor with a meter.
- Refrigerant work and charge changes go to a licensed technician.
More air conditioner guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.