Liquid floods back to compressor on start / liquid refrigerant in cold condenser

What is going on

If liquid refrigerant gets to the compressor on start-up, the usual story is that refrigerant has migrated to the coldest point in the system, which is often the condenser sitting outdoors on a cold night, and then pushes back at startup. This can slug and damage a compressor, so confirm what is happening before you restart the unit repeatedly. Piping details matter here, so call a licensed technician for any refrigerant side changes.

Likely causes

  • No discharge line trap, so liquid can drain back to the compressor
  • Refrigerant migrating from the receiver to the cold condenser, which is the coldest point

Check in this order

  1. Look at the discharge line for a trap, and confirm it is where the manual shows it
  2. Check the condenser outlet for an inverted trap
  3. Look for a check valve between the LAC and the receiver, and make sure it seats and is installed in the right flow direction
  4. Feel the compressor and the condenser outlet when the unit has sat cold to confirm liquid is present
  5. Do not run the compressor repeatedly until the migration is fixed, and have a licensed refrigeration tech make piping changes

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.