Insufficient cooling, frost at outlet of liquid-line filter-drier, both pressures and amps dropping

What is going on

Not cooling enough. Frost at the outlet of the liquid-line filter-drier, with both pressures and amps falling. That's a restricted drier, Scenario 33B. Refrigerant is flashing past the plug and starving the evaporator.

Likely causes

  • Plugged filter-drier causing a restriction
  • Low charge as another possibility
  • Bad metering device as another possibility
  • Kinked or pinched liquid line

Check in this order

  1. Feel for the temperature drop across the drier. A noticeable drop means a restriction.
  2. Compare to gauges and amp draw.
  3. Recover the refrigerant properly.
  4. Replace the drier, evacuate and recharge to spec.
  5. Rule out low charge and a bad metering device.
  6. Licensed tech only for refrigerant work.

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.