Viessmann · Heat pump

EH0E Water-level alarm malfunction

Low severity Vitocal IND-A

What the control is telling you

The water-level sensing voltage is not 5 V, so the LED shows this fault.

Applies to: Models 18XAK, 24XAK, 30XAK, 36XAK, 48XAK, 60XAK

Likely causes

  • Water-level switch not seated properly
  • Broken water-level switch
  • Connection wire fault
  • Faulty indoor main PCB

Test and repair steps

  1. Power off, then restart the unit 2 minutes later.
  2. Check that the water-level switch is inserted properly; reseat it if not.
  3. If the fault remains, replace the water-level switch.
  4. If it still remains, replace the indoor main PCB.
  5. If the unit runs normally, the fault is cleared.

Other codes on the same units

  • EC55 Open or short circuit of temperature sensor (outdoor)
  • EC56 Open or short circuit of temperature sensor (outdoor)
  • EC71 Overcurrent failure of outdoor DC fan motor
  • EC73 Zero-speed failure of outdoor DC fan motor
  • EH00 EEPROM parameter error
  • EH61 Open or short circuit of temperature sensor (indoor)
  • EH62 Open or short circuit of temperature sensor (indoor)
  • EH65 Open or short circuit of temperature sensor (indoor)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: DLFUAA Service Manual (Viessmann Vitocal IND-A), p. 25. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.