Viessmann · Heat pump
EH00/EH0A Indoor unit EEPROM parameter error
What the control is telling you
Indoor unit EEPROM parameter error. Operation lamp flashes 1 time, timer lamp off. The indoor or outdoor main chip is not getting feedback from the EEPROM chip.
Applies to: DLFSOAH09XAK, DLFSOAH18XAK indoor units
Likely causes
- Indoor or outdoor PCB main chip does not receive feedback from the EEPROM chip
Test and repair steps
- Turn off the main power, wait 2 minutes, then turn it back on.
- If the code still shows, replace the indoor main PCB (E0/EA).
- If the code clears, the unit is operating as designed.
Other codes on the same units
- EC 07 Outdoor fan speed outside normal range
- EC 0d Outdoor unit malfunction
- EC 51 Outdoor unit EEPROM parameter error
- EC 52 Condenser coil temperature sensor T3 open or shorted
- EC 53 Outdoor room temperature sensor T4 open or shorted
- EC 54 Compressor discharge temperature sensor TP open or shorted
- EC 55 IGBT temperature sensor TH open or shorted
- EC 56 Evaporator coil outlet temperature sensor T2B open or shorted
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: DLFSOAH service manual, PDF p. 15, 16. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.