Viessmann · Heat pump

EC71 Overcurrent failure of outdoor DC fan motor

High severity Vitocal IND-A

What the control is telling you

Overcurrent on the outdoor DC fan motor. The unit stops and the LED shows the fault.

Applies to: Vitocal IND-A DLFUAA air handler, models 18XAK to 60XAK

Likely causes

  • Fan blocked or hard to turn
  • Wiring fault to the fan motor
  • Faulty fan motor
  • Faulty outdoor PCB

Test and repair steps

  1. Power off, restart after 2 minutes, and check whether the fault returns.
  2. If it returns, shut off the power and rotate the fan by hand.
  3. Remove any obstruction if the fan does not turn easily.
  4. Check the fan motor wiring and correct any improper connections.
  5. Measure the fan motor voltage at the PCB.
  6. Replace the fan motor if it is outside normal parameters.
  7. Replace the main PCB if the voltage is wrong.

Other codes on the same units

  • EC52 Open or short circuit of temperature sensor (outdoor)
  • EC54 Open or short circuit of temperature sensor (outdoor)
  • EC55 Open or short circuit of temperature sensor (outdoor)
  • EC56 Open or short circuit of temperature sensor (outdoor)
  • EC73 Zero-speed failure of outdoor DC fan motor
  • EH00 EEPROM parameter error
  • EH0E Water-level alarm malfunction
  • EH61 Open or short circuit of temperature sensor (indoor)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Viessmann Vitocal IND-A DLFUAA service manual, p. 21. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.