Viessmann · Heat pump

EC56 Open or short circuit of temperature sensor (outdoor)

Medium severity Vitocal IND-A

What the control is telling you

The sampling voltage is below 0.06 V or above 4.94 V, so the sensor reading is out of range.

Applies to: Vitocal IND-A DLFUAA air handler, models 18XAK to 60XAK

Likely causes

  • Open or shorted sensor
  • Poor sensor connection
  • Faulty outdoor PCB

Test and repair steps

  1. Check the connection between the sensor and the PCB.
  2. Ensure the wiring is proper.
  3. Measure the sensor resistance.
  4. Replace the sensor if its value is not acceptable.
  5. Replace the outdoor PCB if the sensor and wiring are good.

Other codes on the same units

  • EC52 Open or short circuit of temperature sensor (outdoor)
  • EC54 Open or short circuit of temperature sensor (outdoor)
  • EC55 Open or short circuit of temperature sensor (outdoor)
  • EC71 Overcurrent failure of outdoor DC fan motor
  • EC73 Zero-speed failure of outdoor DC fan motor
  • EH00 EEPROM parameter error
  • EH0E Water-level alarm malfunction
  • EH61 Open or short circuit of temperature sensor (indoor)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Viessmann Vitocal IND-A DLFUAA service manual, p. 23. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.