F.893 Burner fault: O2 probe malfunction, calibration failed
What the control is telling you
The burner is in a fault state because the O2 probe calibration failed. Same checks as F.892.
Applies to: Vitocrossal 200 CI2
Likely causes
- Flue gas recirculation
- Contaminated combustion air or wrong O2 content
- Blocked venting or air intake
- Condensate blockage or build-up in the heat exchanger
- Dirty combustion air filter
Test and repair steps
- Check for internal and external flue gas recirculation.
- Measure the incoming combustion air with a flue gas analyzer. It should be about 20.7-21% O2.
- Room-air dependent boilers measure at the fan intake during pre-purge and burner operation.
- Ducted combustion air measure at the flap before the fan intake during pre-purge and burner operation.
- Check venting and air intake for blockage and condensate blockage. Look for condensate build-up in the heat exchanger.
- Check the combustion air filter pressure drop. Over 0.6 in w.c. (150 Pa) during post-purge means a dirty filter.
Models that show this code
21 models in Vitocrossal 200 CI2
Other codes on the same units
- F.889 O2 probe malfunction, cyclic probe check failed
- F.890 O2 probe malfunction, cyclic probe check failed (flue gas and air checks)
- F.891 O2 probe not ready in pre/post purge
- F.892 Burner fault: O2 probe malfunction, calibration failed
- F.894 Burner fault: O2 probe malfunction, probe heating
- F.895 Burner fault: O2 probe malfunction, wear
- F.896 Safety chain 1 has responded
- F.897 Safety chain 2 has responded
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocrossal 200 CI2 Service Instructions, p. 73. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.