Viessmann · Boiler

F.891 O2 probe not ready in pre/post purge

High severity Vitocrossal 200 CI2

What the control is telling you

System is in a fault state because the O2 probe is not ready for operation during pre-purge or post-purge.

Applies to: Vitocrossal 200 CI2 boiler with O2 probe

Likely causes

  • Probe not ready for operation in pre/post purge
  • Loose or damaged O2 probe connector or wiring
  • Damaged or contaminated probe tip
  • Faulty O2 probe heater
  • Hardware fault found during pre-purge by the BCU
  • Blocked venting or air intake
  • Condensate blockage or build-up in the heat exchanger
  • Dirty combustion air filter
  • Internal or external flue gas recirculation

Test and repair steps

  1. Check the electric connection to the O2 probe (cable and connectors at the probe).
  2. Check for loose connectors on the BCU and probe, and for damaged or broken pins or wires.
  3. Check the probe tip for damage or contamination, and check that nothing blocks the probe openings.
  4. Check the O2 probe heater resistance of the heating coil should be about 2 to 3 Ohm (pins 3 and 5 on the all-black sensor; pins 2 and 3 on the black-yellow sensor).
  5. Probe check install the O2 probe from a faulting burner into a working burner. If the working burner then shows F.891, the probe is broken. If it starts without F.891, the probe is good and the BCU on the faulty burner should be replaced.
  6. If the fault is intermittent or only in the error history: check the combustion air by measuring at the fan intake (room air) or through the flap (ducted air) during pre-purge and burner operation.
  7. Check for blocked venting and air intake, and for condensate blockage or build-up in the heat exchanger.
  8. Check the pressure drop over combustion air filters; over 0.6 in w.c. (150 Pa) during post-purge means a dirty filter.
  9. Check for internal and external flue gas recirculation.

Models that show this code

21 models in Vitocrossal 200 CI2

100015002000399500750CI2 1000CI2 1500CI2 1500/2000CI2 2000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750

Other codes on the same units

  • F.887 Gas valve test faulty, valve seat V1 faulty
  • F.888 Communication error with Lambda probe controller
  • F.889 O2 probe malfunction, cyclic probe check failed
  • F.890 O2 probe malfunction, cyclic probe check failed (flue gas and air checks)
  • F.892 Burner fault: O2 probe malfunction, calibration failed
  • F.893 Burner fault: O2 probe malfunction, calibration failed
  • F.894 Burner fault: O2 probe malfunction, probe heating
  • F.895 Burner fault: O2 probe malfunction, wear

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Vitocrossal 200 CI2 service instructions, p. 72. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.