Viessmann · Boiler

F.892 Burner fault: O2 probe malfunction, calibration failed

Medium severity Vitocrossal 200 CI2

What the control is telling you

The burner is in a fault state because the O2 probe calibration failed.

Applies to: Vitocrossal 200 CI2

Likely causes

  • Flue gas recirculation
  • Contaminated combustion air or wrong O2 content
  • Blocked venting or air intake
  • Condensate blockage or build-up in the heat exchanger
  • Dirty combustion air filter

Test and repair steps

  1. Check for internal and external flue gas recirculation.
  2. Measure the incoming combustion air with a flue gas analyzer. It should be about 20.7-21% O2.
  3. Room-air dependent boilers measure at the fan intake during pre-purge and burner operation.
  4. Ducted combustion air measure at the flap before the fan intake during pre-purge and burner operation.
  5. Check venting and air intake for blockage and condensate blockage. Look for condensate build-up in the heat exchanger.
  6. Check the combustion air filter pressure drop. Over 0.6 in w.c. (150 Pa) during post-purge means a dirty filter.

Models that show this code

21 models in Vitocrossal 200 CI2

100015002000399500750CI2 1000CI2 1500CI2 1500/2000CI2 2000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750

Other codes on the same units

  • F.888 Communication error with Lambda probe controller
  • F.889 O2 probe malfunction, cyclic probe check failed
  • F.890 O2 probe malfunction, cyclic probe check failed (flue gas and air checks)
  • F.891 O2 probe not ready in pre/post purge
  • F.893 Burner fault: O2 probe malfunction, calibration failed
  • F.894 Burner fault: O2 probe malfunction, probe heating
  • F.895 Burner fault: O2 probe malfunction, wear
  • F.896 Safety chain 1 has responded

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Vitocrossal 200 CI2 Service Instructions, p. 73. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.