Viessmann · Boiler
F.890 O2 probe malfunction, cyclic probe check failed (flue gas and air checks)
What the control is telling you
System is in a fault state because the O2 probe failed its cyclic check. Focus on flue gas recirculation, air contamination, venting and condensate.
Applies to: Vitocrossal 200 CI2 boiler with O2 probe
Likely causes
- Cyclic probe check failed
- Internal or external flue gas recirculation
- Contaminated intake air or O2 content
- Flue gas intake from other devices
- Blocked venting or air intake
- Condensate blockage or build-up in the heat exchanger
- Dirty combustion air filter
- Wind or pressure changes at the installation site
- Venting or air termination not per boiler installation instructions
Test and repair steps
- Check for internal and external flue gas recirculation.
- Check for contaminated intake air and its O2 content.
- Check for flue gas intake from other devices.
- Measure incoming combustion air with a flue gas analyzer; it should be about 20.7 to 21 percent O2. Room air: measure at the fan intake during pre-purge and burner operation. Ducted air: measure through the flap before the fan intake.
- Check for blocked venting and air intake.
- Check for condensate blockage and for condensate build-up in the heat exchanger.
- Check the pressure drop over combustion air filters; over 0.6 in w.c. (150 Pa) during post-purge means a dirty filter.
- Check the installation site for wind or pressure-changing events.
- Verify that the venting and combustion air terminations match the layouts in the boiler installation instructions.
Models that show this code
21 models in Vitocrossal 200 CI2
Other codes on the same units
- F.886 Gas valve test malfunction, VPS pressure not dropping during VPS test
- F.887 Gas valve test faulty, valve seat V1 faulty
- F.888 Communication error with Lambda probe controller
- F.889 O2 probe malfunction, cyclic probe check failed
- F.891 O2 probe not ready in pre/post purge
- F.892 Burner fault: O2 probe malfunction, calibration failed
- F.893 Burner fault: O2 probe malfunction, calibration failed
- F.894 Burner fault: O2 probe malfunction, probe heating
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocrossal 200 CI2 service instructions, p. 72. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.