F.889 O2 probe malfunction, cyclic probe check failed
What the control is telling you
System is in a fault state because the O2 probe failed its cyclic check. Use the steps for a new install or BCU change, or for a fault that appears after running without a previous fault.
Applies to: Vitocrossal 200 CI2 boiler with O2 probe
Likely causes
- Cyclic probe check failed
- Loose or damaged O2 probe connector or wiring
- Damaged or contaminated probe tip
- Faulty O2 probe heater
- Hardware fault found during pre-purge by the BCU
- O2 probe reading differs from flue gas analyzer reading
- Internal or external flue gas recirculation
- Contaminated combustion air
- Blocked venting or air intake
- Condensate blockage or build-up in the heat exchanger
- Dirty combustion air filter
- Wind or pressure changes at the installation site
- Venting or air termination not per boiler installation instructions
Test and repair steps
- If new after installation or after a probe or BCU change: run the burner 2 to 6 minutes, then cause a regular shutdown by removing heat demand. Repeat up to 5 times until the burner runs more than 10 minutes without the fault.
- If the fault appeared after normal running: check the electric connection to the O2 probe (cable and connectors at the probe).
- Check for loose connectors on the BCU and probe, and for damaged or broken pins or wires.
- Check the probe tip for damage or contamination, and check that nothing blocks the probe openings.
- Check the O2 probe heater resistance of the heating coil should be about 2 to 3 Ohm (pins 3 and 5 on the all-black sensor; pins 2 and 3 on the black-yellow sensor).
- Compare the probe O2 value with a flue gas analyzer during operation. With air calibration at 20.8 to 21 percent O2, the difference should be under 0.5 percent. If over 1 percent, try another probe, then another BCU.
- Check for internal and external flue gas recirculation and for flue gas intake from other devices.
- Measure incoming combustion air with a flue gas analyzer; it should be about 20.7 to 21 percent O2. Room air: measure at the fan intake during pre-purge and burner operation. Ducted air: measure through the flap before the fan intake.
- Check for blocked venting and air intake, and for condensate blockage or build-up in the heat exchanger.
- Check the pressure drop over combustion air filters; over 0.6 in w.c. (150 Pa) during post-purge means a dirty filter.
- Check the installation site for wind or pressure-changing events.
- Verify that the venting and combustion air terminations match the layouts in the boiler installation instructions.
Models that show this code
21 models in Vitocrossal 200 CI2
Other codes on the same units
- F.884 Gas valve test malfunction, VPS pressure not rising during filling
- F.885 Gas valve test faulty, valve seat V2 faulty
- F.886 Gas valve test malfunction, VPS pressure not dropping during VPS test
- F.887 Gas valve test faulty, valve seat V1 faulty
- F.888 Communication error with Lambda probe controller
- F.890 O2 probe malfunction, cyclic probe check failed (flue gas and air checks)
- F.891 O2 probe not ready in pre/post purge
- F.892 Burner fault: O2 probe malfunction, calibration failed
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocrossal 200 CI2 service instructions, p. 71. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.