F.63 Flue gas temperature limiter tripped
What the control is telling you
Burner in a fault state after the flue gas temperature limiter responded.
Applies to: Vitodens 200-W B2HE 85, 120, 150, 199
Likely causes
- Low water level
- Wrong expansion tank pre-charge
- Insufficient flow
- 3-way valve fault
Test and repair steps
- Check the system fill level.
- Check expansion tank pre-charge and adjust to system pressure.
- Verify flow is sufficient (flow sensor and circulation pump).
- Test the 3-way diverter valve in the actuator test.
- Vent the system.
- Reset only after the flue system has cooled down.
Models that show this code
4 models in Vitodens 200-W B2HE
Other codes on the same units
- F.574 HC1 room sensor not available
- F.58 Room temperature sensor short circuit
- F.59 Supply voltage too low, burner locked out
- F.62 High limit safety cut-out tripped
- F.666 DHW preheating sensor TS3 open circuit
- F.667 DHW preheating sensor TS3 short circuit
- F.668 DHW reheating sensor TS4 open circuit
- F.669 DHW reheating sensor TS4 short circuit
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions 6167 813-24 (09/2026), Fault messages, p.62-73. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.