Viessmann · Boiler

F.67 Ionization current outside permitted range

High severity Vitodens 200-W B2HE

What the control is telling you

Burner in a fault state; ionization signal out of range.

Applies to: Vitodens 200-W B2HE 85, 120, 150, 199

Likely causes

  • Low gas pressure
  • Gas valve or inlet strainer problem
  • Electrode gap or dirt
  • Faulty fan unit

Test and repair steps

  1. Check gas supply pressure, gas solenoid valve and inlet strainer.
  2. Check ionization electrode clearance to the flame body assembly.
  3. Check electrode and flame body for contamination.
  4. If those do not help, replace the fan unit.
  5. Reset the appliance.

Models that show this code

4 models in Vitodens 200-W B2HE

B2HE-120B2HE-150B2HE-199B2HE-85

Other codes on the same units

  • F.666 DHW preheating sensor TS3 open circuit
  • F.667 DHW preheating sensor TS3 short circuit
  • F.668 DHW reheating sensor TS4 open circuit
  • F.669 DHW reheating sensor TS4 short circuit
  • F.670 Buffer sensor TS3 open circuit
  • F.671 Buffer sensor TS3 short circuit
  • F.672 Thermostat-function sensor TS3 open circuit
  • F.673 Thermostat-function sensor TS3 short circuit

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions 6167 813-24 (09/2026), Fault messages, p.62-73. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.