Viessmann · Boiler

F.629 Heating circuit 4 return sensor lead break, emergency mode

Medium severity Vitocrossal 200 CI2

What the control is telling you

Emergency mode is active for heating circuit 4. The heating circuit pump runs and the mixing valve moves to CLOSED.

Applies to: Vitocrossal 200 CI2 boiler, heating circuit 4

Likely causes

  • Lead break, return temperature sensor, heating circuit 4

Test and repair steps

  1. Check the return temperature sensor and mixing valve 4.
  2. Measure the sensor input on the electronics module (target 3.3V DC with sensor disconnected).

Models that show this code

21 models in Vitocrossal 200 CI2

100015002000399500750CI2 1000CI2 1500CI2 1500/2000CI2 2000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750

Other codes on the same units

  • F.624 Heating circuit 1 return sensor short circuit, emergency mode
  • F.625 Heating circuit 2 return sensor lead break, emergency mode
  • F.626 Heating circuit 2 return sensor short circuit, emergency mode
  • F.627 Heating circuit 3 return sensor lead break, emergency mode
  • F.628 Heating circuit 3 return sensor short circuit, emergency mode
  • F.630 Heating circuit 4 return sensor short circuit, emergency mode
  • F.64 Flame loss during stabilization or operating phase
  • F.65 No or insufficient flame signal at burner start

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Vitocrossal 200 CI2 service instructions, p. 69. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.