Viessmann · Boiler
F.628 Heating circuit 3 return sensor short circuit, emergency mode
What the control is telling you
Emergency mode is active for heating circuit 3. The heating circuit pump runs and the mixing valve moves to CLOSED.
Applies to: Vitocrossal 200 CI2 boiler, heating circuit 3
Likely causes
- Short circuit, return temperature sensor, heating circuit 3
Test and repair steps
- Check the return temperature sensor and mixing valve 3.
- Measure the sensor input on the electronics module (target 3.3V DC with sensor disconnected).
Models that show this code
21 models in Vitocrossal 200 CI2
Other codes on the same units
- F.623 Heating circuit 1 return sensor lead break, emergency mode
- F.624 Heating circuit 1 return sensor short circuit, emergency mode
- F.625 Heating circuit 2 return sensor lead break, emergency mode
- F.626 Heating circuit 2 return sensor short circuit, emergency mode
- F.627 Heating circuit 3 return sensor lead break, emergency mode
- F.629 Heating circuit 4 return sensor lead break, emergency mode
- F.630 Heating circuit 4 return sensor short circuit, emergency mode
- F.64 Flame loss during stabilization or operating phase
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocrossal 200 CI2 service instructions, p. 69. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.