Viessmann · Boiler

F.62 High limit safety cut-out tripped

Critical severity Vitodens 200-W B2HE

What the control is telling you

Burner in a fault state after the high limit safety cut-out responded.

Applies to: Vitodens 200-W B2HE 85, 120, 150, 199

Likely causes

  • Low water level
  • Wrong expansion tank pre-charge
  • Insufficient flow
  • 3-way valve fault
  • Air in system

Test and repair steps

  1. Check the system fill level.
  2. Check expansion tank pre-charge and adjust to system pressure.
  3. Verify flow is sufficient (flow sensor and circulation pump).
  4. Test the 3-way diverter valve in the actuator test.
  5. Vent the system.
  6. Reset the appliance.

Models that show this code

3 models in Vitodens 200-W B2HE

B2HE-120B2HE-150B2HE-85

Other codes on the same units

  • F.57 Room temperature sensor open circuit
  • F.574 HC1 room sensor not available
  • F.58 Room temperature sensor short circuit
  • F.59 Supply voltage too low, burner locked out
  • F.63 Flue gas temperature limiter tripped
  • F.666 DHW preheating sensor TS3 open circuit
  • F.667 DHW preheating sensor TS3 short circuit
  • F.668 DHW reheating sensor TS4 open circuit

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions 6167 813-24 (09/2026), Fault messages, p.62-73. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.