Viessmann · Boiler

F.57 Room temperature sensor open circuit

Low severity Vitodens 200-W B2HE

What the control is telling you

Normal operation but without room temperature influence.

Applies to: Vitodens 200-W B2HE 85, 120, 150, 199

Likely causes

  • Open circuit on room sensor

Test and repair steps

  1. Check the remote control setting in the commissioning assistant.
  2. Check plug and cable of the external room sensor of the heating circuit.
  3. If no external room sensor is fitted, replace the Vitotrol programming unit.

Models that show this code

3 models in Vitodens 200-W B2HE

B2HE-120B2HE-150B2HE-85

Other codes on the same units

  • F.544 HC2 mixed supply sensor open circuit
  • F.545 HC2 mixed supply sensor short circuit
  • F.546 HC3 mixed supply sensor open circuit
  • F.547 HC3 mixed supply sensor short circuit
  • F.548 HC4 mixed supply sensor fault (open circuit)
  • F.549 HC4 mixed supply sensor short circuit
  • F.574 HC1 room sensor not available
  • F.58 Room temperature sensor short circuit

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions 6167 813-24 (09/2026), Fault messages, p.62-73. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.