Viessmann · Boiler
F.546 HC3 mixed supply sensor open circuit
What the control is telling you
Mixer closes; pump keeps running.
Applies to: Vitodens 200-W B2HE 85, 120, 150, 199
Likely causes
- Open circuit sensor
- Wrong commissioning setting
Test and repair steps
- Check supply sensor of mixing valve 3.
- Measure about 3.3 V DC at the sensor input with sensor unplugged.
- Check commissioning assistant setting and ADIO rotary switch.
Models that show this code
4 models in Vitodens 200-W B2HE
Other codes on the same units
- F.538 System return sensor open (SDIO)
- F.540 Condensate back-up in heat cell
- F.544 HC2 mixed supply sensor open circuit
- F.545 HC2 mixed supply sensor short circuit
- F.547 HC3 mixed supply sensor short circuit
- F.548 HC4 mixed supply sensor fault (open circuit)
- F.549 HC4 mixed supply sensor short circuit
- F.57 Room temperature sensor open circuit
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions 6167 813-24 (09/2026), Fault messages, p.62-73. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.