F.361 No or weak flame signal at burner start

High severity Vitodens 200-W B2HE

What the control is telling you

Burner in a fault state.

Applies to: Vitodens 200-W B2HE 85, 120, 150, 199

Likely causes

  • Electrode/cable fault
  • Loose contacts
  • Condensate back-up
  • Contaminants in combustion air

Test and repair steps

  1. Check ionization electrode and cable; check plugs for loose contacts.
  2. Check for condensate back-up.
  3. Deposits on electrodes point to foreign substances in the air: check the room and flue (detergents, cleaners, toiletries).
  4. Reset the appliance.

Models that show this code

3 models in Vitodens 200-W B2HE

B2HE-120B2HE-150B2HE-85

Other codes on the same units

  • F.352 CO limit inside appliance exceeded
  • F.353 Insufficient gas supply, output reduced
  • F.354 Gas modulation valve tolerance outside range
  • F.355 Analogue signal reference check: flame signal at start
  • F.357 Insufficient gas supply
  • F.366 Gas valve supply does not switch off
  • F.367 Gas valve supply does not switch off
  • F.369 Flame loss right after ignition (safety time)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions 6167 813-24 (09/2026), Fault messages, p.62-73. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.