F.359 No ignition spark

High severity Vitodens 100-W

What the control is telling you

Burner is in a fault state because no ignition spark is produced.

Applies to: Vitodens 100-W B1HE/B1KE

Likely causes

  • Damaged ignition electrode insulation
  • No 120 V~ at the ignition module during ignition
  • Faulty ignition module
  • Condensate backup or clog
  • Faulty connecting cables or leads

Test and repair steps

  1. Check whether the ignition electrode insulation is damaged.
  2. Check for 120 V~ at the ignition module during the ignition phase; if absent, replace the BCU burner control unit.
  3. If 120 V~ is present but the fault remains, replace the ignition module.
  4. Check the cables and leads from the ignition module and electrode.
  5. Check the condensate system for backup or clog; replace insulation blocks, electrodes and flame body if needed.
  6. Reset the boiler.

Models that show this code

2 models in Vitodens 100-W

WB1AWB1B

Other codes on the same units

  • a9 Communication fault with OpenTherm device

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Viessmann Vitodens 100-W B1HE/B1KE installation/service manual, p. 77. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.